HVAC control systems can be especially difficult to adjust or tune bec
ause She process gain of the control loop varies with a range of varia
bles, including the control point. For example, if the air flow rate o
ver a hot-water heating coil is cut in half, the ratio of the change i
n outlet temperature to the change in valve position, called the gain
of the coil, will increase significantly. This phenomenon is common in
multizone and variable air volume applications.