The conventional proportional-integral type control system loops for t
he current and extinction angle controllers in high voltage de convert
ers are replaced with fuzzy logic based controls. The two approaches a
re compared using simulations on an electromagnetic transients simulat
ion program. A method to further refine the fuzzy logic formulation to
improve the transient response is presented. The results show that th
e fuzzy logic based approach can provide, at the minimum, a marginal i
mprovement over the P-I based controller.