T. Betz et D. Koenig, FUNDAMENTAL-STUDIES ON VACUUM CIRCUIT-BREAKER ARC QUENCHING LIMITS WITH A SYNTHETIC TEST CIRCUIT, IEEE transactions on dielectrics and electrical insulation, 4(4), 1997, pp. 365-369
The aim of this work is to demonstrate the use of a synthetic test cir
cuit with LC resonant circuits for fundamental experimental work on CB
(vacuum circuit breakers) Studies have been performed on a 36 kV-mode
l CB at test currents of 5 and 10 kA rms aiming at separating the infl
uence of different parameters of the transient recovery voltage such a
s average rate of rise and peak value on the breaking capability. Furt
hermore the effect of the arcing time on the measured are quenching li
mit is presented.