A. Greco et al., R407C AS AN ALTERNATIVE TO R22 IN VAPOR COMPRESSION PLANT - AN EXPERIMENTAL-STUDY, International journal of energy research, 21(12), 1997, pp. 1087-1098
The problem of HCFC22 phase-out in refrigeration plants is analysed, A
comparison is performed between R22 and R407C, The latter seems a pro
mising drop-in substitute. Indeed, its use in existing plants would on
ly require discharge of mineral oil and refilling with a compatible po
lyolester oil. The experimental tests are performed in a plant consist
ing in a water-cooled vapor-compression circuit employed for cooling a
water-glycol mixture in a closed-loop system. Both the thermodynamic
properties and general performance of R407C are comparable with those
of R22. The COP, however, is 5-17% lower, As a consequence, in order t
o provide the same refrigerating load, a plant working with R407C requ
ires higher electric-power consumption. The operational behaviour of R
407C is increasingly better with increasing condensation and evaporati
on temperature. Therefore, R407C is a good R22 substitute in all appli
cations requiring high evaporation temperatures, such as air-condition
ing plants. (C) 1997 by John Wiley & Sons, Ltd.