COOLING LOAD VERSUS COP CHARACTERISTICS FOR AN IRREVERSIBLE AIR REFRIGERATION CYCLE

Authors
Citation
Lg. Chen et al., COOLING LOAD VERSUS COP CHARACTERISTICS FOR AN IRREVERSIBLE AIR REFRIGERATION CYCLE, Energy conversion and management, 39(1-2), 1998, pp. 117-125
Citations number
23
Categorie Soggetti
Energy & Fuels",Mechanics,"Physics, Nuclear",Thermodynamics
ISSN journal
01968904
Volume
39
Issue
1-2
Year of publication
1998
Pages
117 - 125
Database
ISI
SICI code
0196-8904(1998)39:1-2<117:CLVCCF>2.0.ZU;2-5
Abstract
The effect of heat resistance on the performance of an air refrigerati on cycle is analyzed with a finite time heat transfer analysis. The pr esent work extends the recent studies on refrigerator performance by i ncorporating nonisentropic compression and expansion. Relations betwee n cooling load and pressure ratio and between COP (coefficient of perf ormance) and pressure ratio for the air refrigeration cycle in which t he irreversibilities of heat resistance losses in the hot and cold-sid e; heat exchangers and nonisentropic losses in the compression and exp ansion processes are derived. The results show that there exists a max imum value of COP and that the cooling load has a parabolic dependence on COP, unlike the monotonically decreasing behaviour in the case of an endoreversible air refrigeration cycle. Published by Elsevier Scien ce Ltd.