ARCING FAULTS DETECTION ON OVERHEAD LINES FROM THE VOLTAGE SIGNALS

Citation
Kj. Zoric et al., ARCING FAULTS DETECTION ON OVERHEAD LINES FROM THE VOLTAGE SIGNALS, INTERNATIONAL JOURNAL OF ELECTRICAL POWER AND ENERGY SYSTEMS, 19(5), 1997, pp. 299-303
Citations number
5
Categorie Soggetti
Engineering, Eletrical & Electronic
ISSN journal
01420615
Volume
19
Issue
5
Year of publication
1997
Pages
299 - 303
Database
ISI
SICI code
0142-0615(1997)19:5<299:AFDOOL>2.0.ZU;2-V
Abstract
This paper presents a simple algorithm for arcing faults detection on overhead lines. The algorithm is based on the harmonic analysis of the bus voltage signals. It uses only the sine components of the odd high er harmonics of the bus voltage, Such an approach provides the algorit hm with insensitivity to the cosine components of the bus voltage odd higher harmonics which can be generated by current odd cosine higher h armonics, The algorithm can be used for blocking the automatic reclosi ng of lines with permanent faults, A very simple are model has been ad opted. The algorithm was successfully tested with signals recorded on a real power system and signals obtained through computer simulated an d laboratory tests. (C) 1997 Elsevier Science Ltd.