DEFECTIVE INSULATORS IN LIVE WORKING ON A 550 KV COMPACT STEEL LATTICE TOWER

Citation
G. Gela et al., DEFECTIVE INSULATORS IN LIVE WORKING ON A 550 KV COMPACT STEEL LATTICE TOWER, IEEE transactions on power delivery, 12(2), 1997, pp. 783-790
Citations number
18
Categorie Soggetti
Engineering, Eletrical & Electronic
ISSN journal
08858977
Volume
12
Issue
2
Year of publication
1997
Pages
783 - 790
Database
ISI
SICI code
0885-8977(1997)12:2<783:DIILWO>2.0.ZU;2-D
Abstract
Research was conducted to determine the minimum number of healthy insu lator units needed to ensure worker safety in live working on a compac t 550 kV steel lattice tower, A large variety of worksite conditions w as investigated, Test results confirm the conservative nature of the C IGRE formula for defective insulator units, and modifications to the f ormula are suggested. The recommended number of healthy units is 12 in a string of 24 units for the case of live work on the compact 550 kV tower, when the Portable Protective Gap (PPG) is used, Adjustment for altitude should be made above 900 m (3000').