Sp. Websper et al., AN INVESTIGATION INTO BREAKER RECLOSURE STRATEGY FOR ADAPTIVE SINGLE POLE AUTORECLOSING, IEE proceedings. Generation, transmission and distribution, 142(6), 1995, pp. 601-607
The effectiveness of single pole autoreclosure (SPAR) in maintaining p
ower system stability is largely determined by the speed with which se
condary are extinction, and hence autoreclosure, can be achieved. Some
recent work in adaptive autoreclosure has introduced the strong possi
bility of bringing some measure of adjusting dead times by accurately
identifying are extinction times. However, although the secondary are
extinction time provides a good indication of when to reclose, reclosu
re of the circuit breakers immediately following are extinction will n
ormally result in a restrike of the fault. This is because a further f
inite time is required to allow the fault are path to deionise fully,
so that the transmission line may withstand the full system voltage on
reenergisation. The with identifying the concerned additional delay p
eriod (after secondary are extinction), so that in conjunction with ad
aptive autoreclosure techniques, the optimal reclosure time can be det
ermined.