APPLICATION OF NEWTON OPTIMAL POWER-FLOW TO ASSESSMENT OF VAR CONTROLSEQUENCES ON VOLTAGE SECURITY - CASE-STUDIES FOR A PRACTICAL POWER-SYSTEM

Citation
Yy. Hong et al., APPLICATION OF NEWTON OPTIMAL POWER-FLOW TO ASSESSMENT OF VAR CONTROLSEQUENCES ON VOLTAGE SECURITY - CASE-STUDIES FOR A PRACTICAL POWER-SYSTEM, IEE proceedings. Part C. Generation, transmission and distribution, 140(6), 1993, pp. 539-544
Citations number
34
Categorie Soggetti
Engineering, Eletrical & Electronic
ISSN journal
01437046
Volume
140
Issue
6
Year of publication
1993
Pages
539 - 544
Database
ISI
SICI code
0143-7046(1993)140:6<539:AONOPT>2.0.ZU;2-J
Abstract
The application of the Newton optimal power flow (OPF) approach to the assessment of VAR controllers on voltage security in the Taiwan Power Company (TPC) is presented in the paper. Important functions in the d eveloped OPF package were achieved to satisfy dispatching requirements . Cases were studied through use of these functions for the purpose of assessing the effect of the various types of VAR controller while con sidering control sequences. The weakness of traditional OPF packages i s pinpointed in that they only obtain an equilibrium solution without the consideration of a proper control sequence. Several significant co mments are suggested, on the basis of these results, to set up useful criteria for the security dispatch. A practical 251-busbar system (Tai power) is used to illustrate the test results.