SYSTEM SEPARATION EQUIPMENT TO MINIMIZE POWER-SYSTEM INSTABILITY USING GENERATORS ANGULAR-VELOCITY MEASUREMENTS

Citation
Y. Morioka et al., SYSTEM SEPARATION EQUIPMENT TO MINIMIZE POWER-SYSTEM INSTABILITY USING GENERATORS ANGULAR-VELOCITY MEASUREMENTS, IEEE transactions on power delivery, 8(3), 1993, pp. 941-947
Citations number
2
Categorie Soggetti
Instument & Instrumentation","Engineering, Eletrical & Electronic
ISSN journal
08858977
Volume
8
Issue
3
Year of publication
1993
Pages
941 - 947
Database
ISI
SICI code
0885-8977(1993)8:3<941:SSETMP>2.0.ZU;2-Q
Abstract
The purpose of this newly developed equipment is to separate the power system when an out-of-step between two groups of generators within it is predicted. The out-of-step prediction method is based on the gener ator's angular-velocity data measured by electromagnetic sensors and g ears that are fastened directly to the rotors. The equipment was teste d by the large-scale power system simulator APSA (Advanced Power Syste m Analyzer), that is installed in the Kansai Electric Power Co., Inc. The equipment also underwent a field test.