HYDRO-QUEBEC CONCERNS RELATED TO PERFORMANCES OF SF6 CIRCUIT-BREAKERS

Citation
R. Beauchemin et al., HYDRO-QUEBEC CONCERNS RELATED TO PERFORMANCES OF SF6 CIRCUIT-BREAKERS, IEEE transactions on power delivery, 8(3), 1993, pp. 1123-1129
Citations number
5
Categorie Soggetti
Instument & Instrumentation","Engineering, Eletrical & Electronic
ISSN journal
08858977
Volume
8
Issue
3
Year of publication
1993
Pages
1123 - 1129
Database
ISI
SICI code
0885-8977(1993)8:3<1123:HCRTPO>2.0.ZU;2-4
Abstract
Hydro-Quebec's concerns regarding circuit-breaker reliability are pres ented. The first section focuses on two aspects crucial in determining line-charging-current breaking capacity: the arc duration and the tes t circuit configuration. The second part discusses the importance of m anufacturing quality for the arcing contacts, nozzles and gaskets. The third part, which is based on test results obtained for different bre akers, gives the test criteria at 20-degrees-C for simulating breaking tests at -50-degrees-C. Hydro-Quebec's requirements for testing the t ightness of SF6 breakers are set forth in the last section, together w ith a reliable leakage-measuring method.