Wy. Zhang et al., ACTIVE DC FILTER FOR HVDC SYSTEM - A TEST INSTALLATION IN THE KONTI-SKAN DC LINK AT LINDOME CONVERTER STATION, IEEE transactions on power delivery, 8(3), 1993, pp. 1599-1606
The purpose of introducing active dc filters is to meet the more and m
ore stringent requirement from power utilities on limiting telephone i
nterference caused by harmonic currents from HVdc transmission lines,
without unnecessarily increasing the cost of HVdc stations, An active
dc filter installed in the Konti-Skan HVdc link is described. The acti
ve dc filter is connected at the bottom of an existing passive dc filt
er at the Lindome station. The active dc filter includes optic harmoni
c current measuring unit, control system, protection and supervision s
ystem, PWM power amplifier, high-frequency transformer, surge arrester
, and coupling apparatuses. The active dc filter has small physical si
ze and occupies small ground area. The performance of the active dc fi
lter for eliminating the disturbing harmonics is excellent. To achieve
comparable results by passive filters would require something like te
n times more high voltage equipment.