Dj. Moschandreas et al., INDOOR AIR-QUALITY AND THE VARIABLE-AIR-VOLUME BYPASS FILTRATION SYSTEM - CHAMBER EXPERIMENT, Environment international, 22(2), 1996, pp. 149-158
Two series of experiments were performed in an ail aluminum chamber un
der controlled conditions to investigate whether the variable-air-volu
me/bypass filtration system (VAV/BPFS) reduces indoor air pollutant co
ncentrations relative to a conventional variable-air-volume (VAV) syst
em. Twelve short-term experiments (100 min) were performed for each ve
ntilation system using indoor sources and one energy load. Also, twelv
e long-term experiments (240 min) were performed with the VAV/BPFS and
conventional VAV system using indoor air pollution sources emitting i
ntermittently and energy load increasing in a stepwise process. Cigare
ttes and deodorants were used to simulate activities in the chamber. F
our energy loads (400, 800, 1200, and 1900 W) were used to simulate th
e presence of occupants in the chamber. Results show that, under contr
olled experimental conditions, the difference between VAV/BPFS system
acid VAV system in reducing indoor air pollutant concentration is stat
istically significant. The particulate matter VAV/BPFS total effective
removal rate was 50% higher than the corresponding VAV PM total effec
tive removal rate. Also, the VAV/BPFS total volatile organic compound
total effective removal rate was 20% higher than that of the VAV syste
m. These chamber results indicate that the VAV/BPFS system is a promis
ing alternative to the conventional VAV system because, under the cond
itions tested, it is capable of reducing and maintaining good indoor a
ir quality and decreasing outdoor supply air rate.