Pj. Moore et al., MODEL SYSTEM TESTS ON A NEW NUMERIC METHOD OF POWER-SYSTEM FREQUENCY-MEASUREMENT, IEEE transactions on power delivery, 11(2), 1996, pp. 696-701
A numeric technique for the evaluation of power system frequency has b
een implemented on a TMS320C31 digital signal processor, The frequency
measuring equipment has been tested on programmable relay testing equ
ipment, using known reference signals, and on a micromachine based pow
er system simulator, The results show the frequency measuring equipmen
t gives fast and accurate measurement under both steady-state and dyna
mic conditions. The response of the equipment to instantaneous changes
in phase and amplitude is found to be undesirable if the algorithm is
to be applied to frequency measuring protection relays.