Y. Yamagata et al., SUPPRESSION OF VFT IN 1100K V-GIS BY ADOPTING RESISTOR-FITTED DISCONNECTOR, IEEE transactions on power delivery, 11(2), 1996, pp. 872-880
With 1000kV transmission lines planned in Japan, very fast transient (
VFT) phenomena will be suppressed by installing a resistor in a discon
nector of gas insulated switchgear (GIS). In this paper the VFT overvo
ltage suppressing effect of the resistor and the duty required of the
resistor are clarified. A 1100kV resistor-fitted disconnector was test
ed by constructing a charging current interruption test circuit. It ha
s been clarified that the disconnector accepts the required duty. The
disconnector tested here will be used for the field test.