ANALYSIS OF LINEAR GROUND ELECTRODES PLACED IN VERTICAL 3-LAYER EARTH

Citation
Pd. Rancic et al., ANALYSIS OF LINEAR GROUND ELECTRODES PLACED IN VERTICAL 3-LAYER EARTH, IEEE transactions on magnetics, 32(3), 1996, pp. 1505-1508
Citations number
14
Categorie Soggetti
Engineering, Eletrical & Electronic","Physics, Applied
ISSN journal
00189464
Volume
32
Issue
3
Year of publication
1996
Pages
1505 - 1508
Database
ISI
SICI code
0018-9464(1996)32:3<1505:AOLGEP>2.0.ZU;2-U
Abstract
The current distribution, line leakage current density, grounding admi ttance/impedance, surface potential and magnetic field distribution of linear ground electrodes (LGE) in inhomogeneous earth of vertical thr ee-layer stratification are presented. This is achieved by using quasi -stationary expressions for potential and system of integral equations of two potentials (SIE-TP).