Yy. Hsu et al., EXPERIENCE WITH THE IDENTIFICATION AND TUNING OF EXCITATION SYSTEM PARAMETERS AT THE 2ND NUCLEAR-POWER-PLANT OF TAIWAN-POWER-COMPANY, IEEE transactions on power systems, 11(2), 1996, pp. 747-753
Experience with the identification and tuning of exciter constants for
a generating unit at the Second Nuclear Power Plant of Taiwan Power C
ompany is reported. Field test is first performed on the excitation sy
stem with the generator open-circuited. Since the field test results d
iffer from the computer simulation results using manufacturer's consta
nts, we first modify the manufacturer's constants based on our previou
s experience to reach a preliminary set of parameters for the excitati
on system. Then a hybrid nonlinear simulation-sensitivity matrix metho
d is developed to further refine the excitation system parameters. The
exciter constants are tuned in order to give better dynamic response
before a power system stabilizer is applied to the generator. Field te
sts are then performed in order to compare the dynamic response of the
generator without and with power system stabilizer.