OPTIMAL TRANSFORMER ALLOCATION UNDER SINGLE-CONTINGENCY

Citation
Lc. Leung et al., OPTIMAL TRANSFORMER ALLOCATION UNDER SINGLE-CONTINGENCY, IEEE transactions on power systems, 11(2), 1996, pp. 1046-1051
Citations number
13
Categorie Soggetti
Engineering, Eletrical & Electronic
ISSN journal
08858950
Volume
11
Issue
2
Year of publication
1996
Pages
1046 - 1051
Database
ISI
SICI code
0885-8950(1996)11:2<1046:OTAUS>2.0.ZU;2-9
Abstract
Under the single-contingency environment where interdependencies are i nherent, allocating transformers to substations ought to take on a sys tem approach In this paper, we present a multi-year mathematical progr amming model which determines the optimal allocation of transformers o ver a planning horizon. The possibility of relocating transformers fro m substations with low utilizations will be explicitly explored. To me et load demand, the model will identify the least-cost allocation and/ or relocation of transformers. It mill ensure that each substation's s ingle-contingency capacity exceeds its load forecast The alternatives to he evaluated include combinations of: additions via purchase, reloc ations from a transformer storage, and relocations within the network. Fort Myers, a small district of Florida Power and Light is studied as a ease example.