A TIME-DOMAIN 3-PHASE POWER-SYSTEM IMPEDANCE MODELING APPROACH FOR HARMONIC FILTER ANALYSIS

Citation
Aa. Girgis et al., A TIME-DOMAIN 3-PHASE POWER-SYSTEM IMPEDANCE MODELING APPROACH FOR HARMONIC FILTER ANALYSIS, IEEE transactions on power delivery, 8(2), 1993, pp. 504-510
Citations number
13
Categorie Soggetti
Instument & Instrumentation","Engineering, Eletrical & Electronic
ISSN journal
08858977
Volume
8
Issue
2
Year of publication
1993
Pages
504 - 510
Database
ISI
SICI code
0885-8977(1993)8:2<504:AT3PIM>2.0.ZU;2-H
Abstract
This paper presents a time-domain method for impedance modeling of an unbalanced, three-phase. power transmission and distribution network u sing three-phase measurements of bus voltage and injected current wave forms. An impedance model seen at a bus where a harmonic filter is to be installed is calculated for each harmonic frequency and the effect of placing the filter at the bus is then analyzed at these frequencies . As the configuration or operating condition of the power system vari es, the estimated model changes accordingly, provided updated measurem ents are available. Hence, the effect of the harmonic filter under dif ferent system configurations or operating conditions can be analyzed a nd the information from this analysis can be used for on-line harmonic filter control. Impedance models estimated by the proposed method hav e been applied in filter design and performance analysis with actual r ecorded data, and the results are presented in this paper.