F. Gubina et al., FAST CONTINGENCY EVALUATION BY MEANS OF THE IMPROVED ADJOINT NETWORK METHOD, INTERNATIONAL JOURNAL OF ELECTRICAL POWER AND ENERGY SYSTEMS, 18(6), 1996, pp. 377-383
In this paper, an improvement of the adjoint network (AN) method based
on the Tellegen theorem for calculation of power system variables fol
lowing various contingencies is presented. A new model of PV nones is
developed and the response of PV nones to line as well as generator ou
tages is modelled accordingly. Furthermore, an improved computational
scheme is derived that enables a fast single step evaluation of post c
ontingency power system variables. Example cases of test and practical
systems show that the improved adjoint network (IAN) method offers an
efficient tool for on-line contingency analysis due to its improved a
ccuracy, and computational effort in comparison with the widely, accep
ted 1P1Q approach based on fast decoupled power flow (FDPF). (C) 1996
Elsevier Science Ltd.