PROPOSED ENERGY-EFFICIENT AIR-CONDITIONING SYSTEM USING LIQUID DESICCANT

Citation
Aa. Kinsara et al., PROPOSED ENERGY-EFFICIENT AIR-CONDITIONING SYSTEM USING LIQUID DESICCANT, Applied thermal engineering, 16(10), 1996, pp. 791-806
Citations number
21
Categorie Soggetti
Engineering, Mechanical",Mechanics,Thermodynamics
Journal title
ISSN journal
13594311
Volume
16
Issue
10
Year of publication
1996
Pages
791 - 806
Database
ISI
SICI code
1359-4311(1996)16:10<791:PEASUL>2.0.ZU;2-W
Abstract
Energy consumption due to conventional air-conditioning is very high, especially in hot, humid areas. The total air-conditioning cooling loa d can be divided into sensible and latent parts. Liquid desiccant solu tions have the property of holding water vapor, therefore they can be used to overcome the latent part of the air-conditioning cooling load. In this work, an energy-efficient system is proposed to reduce energy consumption in air-conditioning (A/C) systems using CaCl2 solution as a liquid desiccant. The proposed system consists mainly of two packed beds, a heat pump, air washers and a cooling coil. Mathematical model ing of various components and fluid properties of the proposed system was undertaken. A computer program was prepared to study the system pe rformance under different conditions. Over most of the conditions at w hich the program was tested, the proposed system was found to be more energy-efficient than a conventional A/C system. Copyright (C) 1996 El sevier Science Ltd