Abstract
This paper describes test results and mitigation methods of electromag netic interference (EMI) on control and low voltage circuits in substa tions caused by air disconnect switch operation. The tests are focused on a comparison between unshielded and shielded circuits from capacit ively coupled voltage transformers (CCVT) and other equipment circuits in the vicinity. New test data are presented comparing unshielded and shielded cables and transient currents on all connections to the CCVT including the pedestal and ground strap. The paper gives a practical and understandable explanation of the causes of EMI in substations and how shielded cable and parallel ground conductors reduce interference . Design guidelines are listed in the Conclusion.