Ta. Bellei et al., EVALUATING CAPACITOR-SWITCHING DEVICES FOR PREVENTING NUISANCE TRIPPING OF ADJUSTABLE-SPEED DRIVES DUE TO VOLTAGE MAGNIFICATION, IEEE transactions on power delivery, 11(3), 1996, pp. 1373-1378
Nuisance overvoltage tripping of pulse-width modulated adjustable-spee
d drives, due to switching of shunt capacitor banks at a utility's sub
station and the subsequent voltage magnification which can occur at an
industrial customer's utilization-voltage bus, is discussed. Adjustab
le-speed drive design considerations affecting transient overvoltage r
ide-through capability are identified and discussed, A comparative eva
luation of three switching devices equipped with transient overvoltage
control, namely, circuit breakers with pre-insertion resistors, circu
it switchers with highly damped pre-insertion inductors, and controlle
d closing devices, is presented.