APPLICATION OF PORTABLE PROTECTIVE GAPS FOR LIVE WORK ON COMPACT 550 KV TRANSMISSION-LINES

Citation
G. Gela et al., APPLICATION OF PORTABLE PROTECTIVE GAPS FOR LIVE WORK ON COMPACT 550 KV TRANSMISSION-LINES, IEEE transactions on power delivery, 11(3), 1996, pp. 1419-1429
Citations number
9
Categorie Soggetti
Engineering, Eletrical & Electronic
ISSN journal
08858977
Volume
11
Issue
3
Year of publication
1996
Pages
1419 - 1429
Database
ISI
SICI code
0885-8977(1996)11:3<1419:AOPPGF>2.0.ZU;2-D
Abstract
This paper presents result of research on the application of a Portabl e Protective Gap (PPG) to live work on a compact 550 kV steel lattice tower. The objective of the research was to provide experimental evide nce which confirms the needed coordination of the PPG sparkover charac teristics with the sparkover characteristics of the worksite on the co mpact tower during live work. Sparkover characteristics of the worksit e are strongly affected by the presence of the worker, the live workin g tools, and damaged insulators.