IMPROVEMENT OF TRANSIENT-RESPONSE BY MEANS OF VARIABLE SET-POINT WEIGHTING

Authors
Citation
Cc. Hang et Ls. Cao, IMPROVEMENT OF TRANSIENT-RESPONSE BY MEANS OF VARIABLE SET-POINT WEIGHTING, IEEE transactions on industrial electronics, 43(4), 1996, pp. 477-484
Citations number
13
Categorie Soggetti
Instument & Instrumentation","Engineering, Eletrical & Electronic
ISSN journal
02780046
Volume
43
Issue
4
Year of publication
1996
Pages
477 - 484
Database
ISI
SICI code
0278-0046(1996)43:4<477:IOTBMO>2.0.ZU;2-S
Abstract
A new approach is introduced for speeding up the transient set point r esponse of a control system by adapting the set point weighting factor in the controller. For a proportional-integral-derivative (PLD) contr oller, the initial set point weighting factor, the instants at which t his factor should be varied, and the adapted value of the set point we ighting factor are all given by a set of correlation formulae which ca n be used in conjunction with the refined Ziegler-Nichols tuning formu la, Analysis has also led to an equivalent block diagram more suitable for its implementation as a set point filter with a variable zero in its transfer function.