VOLTAGE OSCILLATORY INSTABILITY CAUSED BY INDUCTION-MOTOR LOADS

Citation
Fp. Demello et Jw. Feltes, VOLTAGE OSCILLATORY INSTABILITY CAUSED BY INDUCTION-MOTOR LOADS, IEEE transactions on power systems, 11(3), 1996, pp. 1279-1284
Citations number
4
Categorie Soggetti
Engineering, Eletrical & Electronic
ISSN journal
08858950
Volume
11
Issue
3
Year of publication
1996
Pages
1279 - 1284
Database
ISI
SICI code
0885-8950(1996)11:3<1279:VOICBI>2.0.ZU;2-4
Abstract
Isolated power systems which fit the structure of a single equivalent generator supplying an equivalent composite load can experience a volt age oscillatory instability entirely traceable to effects of induction motor loads interacting with automatic voltage regulators. This scena rio is one where an AVR properly tuned for open circuit conditions is not necessarily well tuned for the on load condition. The phenomenon i s explained and a simple solution through AVR compensation is suggeste d.