CONTACT RESISTANCE IN AIR-COOLED PLATE FIN-TUBE AIR-CONDITIONING CONDENSERS

Citation
Re. Critoph et al., CONTACT RESISTANCE IN AIR-COOLED PLATE FIN-TUBE AIR-CONDITIONING CONDENSERS, International journal of refrigeration, 19(6), 1996, pp. 400-406
Citations number
5
Categorie Soggetti
Engineering, Mechanical",Thermodynamics
ISSN journal
01407007
Volume
19
Issue
6
Year of publication
1996
Pages
400 - 406
Database
ISI
SICI code
0140-7007(1996)19:6<400:CRIAPF>2.0.ZU;2-1
Abstract
Test equipment and procedures have been developed to measure the heat transfer performance of an industry-standard wavy plate fin-tube conde nser, and to compare it with alternative designs, Two test rigs were e mployed:one used direct electric heating, and the other used an R22 th ermosyphon. Analysis revealed that the standard production heat exchan ger suffered from excessive fin-tube resistance. This was confirmed by sectioning and microscopic examination. Seven different designs were compared at the same Reynolds number. The results were analysed to iso late the air-side heat transfer coefficient. Copyright (C) 1996 Elsevi er Science Ltd and IIR