THEORETICAL-ANALYSIS AND OPTIMIZATION OF A DOUBLE-EFFECT SERIES-FLOW-TYPE ABSORPTION CHILLER

Citation
Gp. Xu et al., THEORETICAL-ANALYSIS AND OPTIMIZATION OF A DOUBLE-EFFECT SERIES-FLOW-TYPE ABSORPTION CHILLER, Applied thermal engineering, 16(12), 1996, pp. 975-987
Citations number
14
Categorie Soggetti
Engineering, Mechanical",Mechanics,Thermodynamics
Journal title
ISSN journal
13594311
Volume
16
Issue
12
Year of publication
1996
Pages
975 - 987
Database
ISI
SICI code
1359-4311(1996)16:12<975:TAOOAD>2.0.ZU;2-6
Abstract
A thermodynamic analysis was carried out to study the effect of design parameters, including heat recovery ratio and solution circulation ra tio, on the performance of a double-effect absorption chiller of the s eries-flow-type using water-lithium bromide as the working fluid. Incr eases in the heat recovery ratios of the high-temperature heat exchang er and the low-temperature heat exchanger and/or decreases in the solu tion circulation ratio improved the coefficient of performance. An inc rease in the heat recovery ratio of the high-temperature heat exchange r increased the total heat transfer area of the absorption chiller. Th e optimum design and operating conditions of a double-effect absorptio n chiller are suggested based on this cycle simulation analysis. Copyr ight (C) 1996 Elsevier Science Ltd.