EHV TRANSFORMER BANK UNBALANCE - PRACTICAL ISSUES AND SOLUTIONS

Citation
R. Gutman et Lb. Wagenaar, EHV TRANSFORMER BANK UNBALANCE - PRACTICAL ISSUES AND SOLUTIONS, IEEE transactions on power delivery, 11(4), 1996, pp. 1830-1835
Citations number
9
Categorie Soggetti
Engineering, Eletrical & Electronic
ISSN journal
08858977
Volume
11
Issue
4
Year of publication
1996
Pages
1830 - 1835
Database
ISI
SICI code
0885-8977(1996)11:4<1830:ETBU-P>2.0.ZU;2-D
Abstract
An unconventional tap configuration has been implemented in AEP's Sout h Canton 765/345/34.5 kV, 3-500 MVA transformer bank to counter the co mbined effects of impedance mismatch within the bank and natural unbal ance of the extra-high-voltage (EHV) transmission system. These effect s manifest themselves as unequal phase voltages and loadings and as el evated neutral and tertiary circulating currents in the bank, capable of reaching high magnitudes during heavy loading conditions. This pape r describes the South Canton bank unbalance, the concerns it raised, a nd the actions taken by AEP to control its possible adverse effects on the integrity and operation of the South Canton Station facilities.