GENERAL EXPRESSION FOR CURRENT TRANSFORMER

Citation
K. Yanagida et al., GENERAL EXPRESSION FOR CURRENT TRANSFORMER, JPN J A P 1, 35(10), 1996, pp. 5530-5538
Citations number
2
Categorie Soggetti
Physics, Applied
Volume
35
Issue
10
Year of publication
1996
Pages
5530 - 5538
Database
ISI
SICI code
Abstract
The mechanism of the current transformer is analyized, and its express ion is derived as a complex function of the frequency spectrum or as a real function of the time evolution. These formulae include the effec t of magnetic material, which is usually a part of the current transfo rmer, and cause a multiple droop phenomenon in the time evolution. It becomes clear that the multiple droop phenomenon is enhanced in the ca se of a few turns of secondary windings, such as in a wall current mon itor. In the case of many turns of secondary windings, the longest dro op component becomes dominant, and the remaining shorter droop compone nts disappear.