EVALUATION OF 230 KV HPFF PIPE-TYPE CABLE WITH WRINKLED AND CREASED INSULATING TAPES

Citation
Gw. Seman et al., EVALUATION OF 230 KV HPFF PIPE-TYPE CABLE WITH WRINKLED AND CREASED INSULATING TAPES, IEEE transactions on power delivery, 10(1), 1995, pp. 53-61
Citations number
8
Categorie Soggetti
Engineering, Eletrical & Electronic
ISSN journal
08858977
Volume
10
Issue
1
Year of publication
1995
Pages
53 - 61
Database
ISI
SICI code
0885-8977(1995)10:1<53:EO2KHP>2.0.ZU;2-R
Abstract
Severe collapse wrinkles and circumferential creases were discovered i n the cellulose paper insulating tapes of a newly installed HPFF pipe- type cable during splicing and terminating. An evaluation program was developed to assess the electrical and mechanical integrity of the cab le having wrinkled and creased insulating tapes. The test results indi cated that the cable would perform satisfactorily in service.