MEASUREMENT OF CABLE SWITCHING TRANSIENTS IN UNDERGROUND DISTRIBUTION-SYSTEMS

Citation
Ra. Walling et al., MEASUREMENT OF CABLE SWITCHING TRANSIENTS IN UNDERGROUND DISTRIBUTION-SYSTEMS, IEEE transactions on power delivery, 10(1), 1995, pp. 534-539
Citations number
6
Categorie Soggetti
Engineering, Eletrical & Electronic
ISSN journal
08858977
Volume
10
Issue
1
Year of publication
1995
Pages
534 - 539
Database
ISI
SICI code
0885-8977(1995)10:1<534:MOCSTI>2.0.ZU;2-H
Abstract
Routine operation of loadbreak elbows and disconnects to switch underg round distribution cables results in transient overvoltages. Presented are the results and analyses of field tests performed in two 24.94 kV systems where transient voltages were recorded during switching opera tions. Traveling wave propagation characteristics in the cables, the i nfluence of underground distribution system topology, and switching de vice are behavior are discussed. Conclusions are reached regarding the severity of the switching overvoltages.