Utility engineers often need nonlinear transformer models in order to
investigate power system transient events. Methods exist to create acc
urate wideband reduced order linear transformer models, however, to da
te a method of creating a reduced order wideband nonlinear transformer
model has not been presented. This paper describes a technique that s
tarts with a detailed nonlinear transformer model used for insulation
design studies and reduces its order so that it can be used convenient
ly in EMTP. The method is based on linearization of the core's saturab
le characteristic during each solution time intervals. The technique u
ses Kron's reduction approach in each solution time interval. A can be
applied to any nonlinear lumped parameter network which uses electric
parameter analogies (i.e., FEM networks). This paper outlines the non
linear reduction technique. An illustrative example is given using the
transient voltage response during saturation for a 785/345/34.5kV, YY
D 500 MVA single phase autotransformer.