O. Bottauscio et al., POWER-FACTOR IN SHORT-CIRCUIT TESTS - DETERMINATION BY CURRENT ZERO CROSSINGS, European transactions on electrical power engineering, 4(6), 1994, pp. 533-536
The paper describes a method for the determination of the power factor
in short-circuit tests based on the analysis of the current behaviour
The knowledge of the first two zero-crossing instants of the current
permits the computation of the power factor with a satisfactory level
of accuracy. The method can be easily adopted in short-circuit test la
boratories equipped with digital acquisition and processing systems.