Zq. Wu et Kl. Lo, OPTIMAL CHOICE OF FIXED AND SWITCHED CAPACITORS IN RADIAL DISTRIBUTORS WITH DISTORTED SUBSTATION VOLTAGE, IEE proceedings. Generation, transmission and distribution, 142(1), 1995, pp. 24-28
The problem of optimal choice of fixed and switched capacitors in radi
al distributors with distorted substation voltages is formulated and s
olved by decomposition through isolated subproblems. The maximum sensi
tivities selection (MSS) method, which is used to solve the optimisati
on problem of the subproblems with discrete variables, is proposed. Th
e results of a test distributor show that harmonic voltages in the sub
station voltage affects the capacitance of the optimal shunt capacitor
s. By combining system harmonic forecasting with the method in this pa
per, the harmonics amplification due to shunt capacitors can be reduce
d to the minimum level.