K. Abrahamsson et al., DESIGN AND EXPERIMENTAL PERFORMANCE EVALUATION OF AN ABSORPTION HEAT TRANSFORMER WITH SELF-CIRCULATION, Heat recovery systems & CHP, 15(3), 1995, pp. 257-272
Citations number
NO
Categorie Soggetti
Energy & Fuels","Engineering, Mechanical",Mechanics,Thermodynamics
A 10 kW experimental absorption heat transformer unit operating with s
elf-circulation has been thoroughly tested. The self-circulation is ob
tained according to the thermosyphon principle. The pressure differenc
e in the unit is achieved through a difference in hydrostatic pressure
s. Theoretical relationships for the pressure profiles within the diff
erent components of the heat transformer have been derived. Stabilisin
g the self-circulation has been the primary objective in this work, ra
ther than the optimisation of the efficiency of heating and cooling ar
eas. A satisfactory stable operation with self-circulation has been ac
hieved. A reference heat transformer plant, delivering 100 kW, has bee
n designed and installed in a major pulp and paper mill. This unit is
directly incorporated with one of the evaporation plants of the mill.
Plant operation data obtained under real industrial conditions are pre
sented.