EVALUATION OF PARTIAL DISCHARGE DETECTION TECHNIQUES ON HYDRO-GENERATORS IN THE AUSTRALIAN SNOWY MOUNTAINS SCHEME TUMUT-1 CASE-STUDY

Citation
Jwl. Simpson et al., EVALUATION OF PARTIAL DISCHARGE DETECTION TECHNIQUES ON HYDRO-GENERATORS IN THE AUSTRALIAN SNOWY MOUNTAINS SCHEME TUMUT-1 CASE-STUDY, IEEE transactions on energy conversion, 10(1), 1995, pp. 18-24
Citations number
10
Categorie Soggetti
Engineering, Eletrical & Electronic","Energy & Fuels
ISSN journal
08858969
Volume
10
Issue
1
Year of publication
1995
Pages
18 - 24
Database
ISI
SICI code
0885-8969(1995)10:1<18:EOPDDT>2.0.ZU;2-J
Abstract
An evaluation of partial discharge detection techniques used on the Un it 3 hydro generator stator windings at Tumut 1 Power Station in the S nowy Mountains Scheme of Australia is presented. Measurements were mad e with an RF slot probe, Robinson ERA Model 5 detector, Ontario Hydro PDA-H detector and a recently developed partial discharge site locatio n (PDSL) system before and after removal of coils. Good agreement was found between all methods with the PDSL system achieving high accuracy in identifying individual high discharging coil sides.