THEORETICAL PERFORMANCE OF HCFC123 AS AN ALTERNATIVE TO CFC11

Citation
Sam. Said et al., THEORETICAL PERFORMANCE OF HCFC123 AS AN ALTERNATIVE TO CFC11, Energy, 20(3), 1995, pp. 205-208
Citations number
4
Categorie Soggetti
Energy & Fuels","Engineering, Chemical
Journal title
EnergyACNP
ISSN journal
03605442
Volume
20
Issue
3
Year of publication
1995
Pages
205 - 208
Database
ISI
SICI code
0360-5442(1995)20:3<205:TPOHAA>2.0.ZU;2-Q
Abstract
Based on the thermodynamic properties of HCFC123 obtained by using a m odified Benedict-Webb-Rubin (MBWR) equation of state fit to experiment al measurements, the theoretical performance of HCFC123 has been asses sed as an alternative to CFC11 by using standard refrigeration paramet ers, including pressure ratio, specific compressor displacement, coeff icient of performance, and shaft power. This study indicates that a CF C11 compressor working with HCFC123 will have lower adiabatic head ris e, efficiency and volume flow. This performance difference should not exclude HCFC123 as an alternative to CFC11 since most of the existing machines are oversized for a particular application and thus performan ce attained with HCFC123 could be adequate.