Ty. Guo et al., IDENTIFICATION OF MODEL PARAMETERS OF EXCITATION SYSTEM AND POWER-SYSTEM STABILIZER OF MINGTAN-NUMBER-6 VIA FINALIZATION FIELD-TESTS, IEEE transactions on power systems, 10(2), 1995, pp. 795-802
Experiences with the model parameter identification of the excitation
system (EXS) and the power system stabilizer (PSS) for Mingtan#6 pumpe
d storage generation unit of. Taiwan Power System are presented in thi
s paper. The input-output data corresponding to each block of the EXS
and PSS were obtained when the finalization tests of this unit were pe
rformed. The generalized least squares (GLS) approach is introduced an
d employed to identify the desired parameters of the noisy excitation
system and PSS models. In this method, the reduction technique of bias
ed estimates due to the non-white. (correlated) identification residua
l is also applied to improve the accuracy of identification. The resul
ts of the parameter estimation are satisfactory. The GLS parameter ide
ntification method using the measured data at finalization tests is th
en suggested from the viewpoint of economy and engineering.