Mr. Iravani et Aa. Edris, EIGEN ANALYSIS OF SERIES COMPENSATION SCHEMES REDUCING THE POTENTIAL OF SUBSYNCHRONOUS RESONANCE, IEEE transactions on power systems, 10(2), 1995, pp. 876-881
Reference [1] describes a new concept for mitigation of the phenomenon
of subsynchronous resonance (SSR) based on asymmetrical series capaci
tor compensation at SSR frequencies. The studies reported in [1] are b
ased on a digital time-domain simulation technique. This paper provide
s a quantitative evaluation of the concept using a novel eigen analysi
s approach. The eigen analysis approach represents the mathematical mo
dels of power system components in the three-phase basis, and can eval
uate the impacts of asymmetry and imbalance on the system dynamics in
the subsynchronous frequency range. The study results restate technica
l feasibility of the proposed SSR countermeasure. This paper opens the
avenue for examination of active power filter topologies to introduce
artificial asymmetry at SSR frequencies to counteract torsional oscil
lations.