Hj. Linde et al., ERADICATION OF LEGIONELLA SPP FROM A WARM WATER DISTRIBUTION-SYSTEM -A DOCUMENTATION OF OWN EXPERIENCES WITH THERMAL DISINFECTION, Zentralblatt fur Hygiene und Umweltmedizin, 197(5), 1995, pp. 441-451
A nosocomial case of Legionellosis in a recently built hospital was th
e reason for an investigation and thermal disinfection of the complete
warm water distribution system. Furthermore weak points in the tubing
of the warm water system, which promoted the contamination of potable
water, were eliminated as far as technically possible. A lasting redu
ction of the numbers of Legionella spp. isolated could be measured (fa
ctor 10-1000), but a complete decontamination of the warm water distri
bution system was not possible. As Legionella spp. may cause serious i
nfections in immunodeficient patients, additional measures for the dis
infection of the hospital water distribution system must be taken into
consideration.