PD DETECTION AND LOCALIZATION BY MEANS OF ACOUSTIC MEASUREMENTS ON HYDROGENERATOR STATOR BARS

Citation
R. Bozzo et al., PD DETECTION AND LOCALIZATION BY MEANS OF ACOUSTIC MEASUREMENTS ON HYDROGENERATOR STATOR BARS, IEEE transactions on dielectrics and electrical insulation, 2(4), 1995, pp. 660-666
Citations number
25
Categorie Soggetti
Engineering, Eletrical & Electronic
ISSN journal
10709878
Volume
2
Issue
4
Year of publication
1995
Pages
660 - 666
Database
ISI
SICI code
1070-9878(1995)2:4<660:PDALBM>2.0.ZU;2-O
Abstract
Acoustic partial discharge detection appears useful for the location o f PD sources within various kinds of insulating systems. The usefulnes s of such a method to locate discharge sources in hydrogenerator stato r bars is illustrated. The adopt,ed measuring procedure, based on two piezo-electric transducers positioned on a bar, allows the identificat ion of the discharge site position within an error range of similar to 2 cm. Such a measuring procedure appears useful as a diagnostic tool in quality control for bars that do not pass the specified acceptance test or in the development of new insulating systems. The measurement circuit and the relevant test procedure are presented. Further comment s about the measured acoustic velocities of the acquired signals are g iven.