PERFORMANCE OF DIFFERENT WORKING FLUIDS IN TRANSFER-TANK OPERATED VAPOR ABSORPTION-REFRIGERATION SYSTEMS

Citation
G. Karthikeyan et al., PERFORMANCE OF DIFFERENT WORKING FLUIDS IN TRANSFER-TANK OPERATED VAPOR ABSORPTION-REFRIGERATION SYSTEMS, Renewable energy, 6(7), 1995, pp. 835-842
Citations number
7
Categorie Soggetti
Energy & Fuels
Journal title
ISSN journal
09601481
Volume
6
Issue
7
Year of publication
1995
Pages
835 - 842
Database
ISI
SICI code
0960-1481(1995)6:7<835:PODWFI>2.0.ZU;2-W
Abstract
A vapour absorption refrigeration system (VARS) in which a transfer ta nk replaces the conventional solution pump is analysed. Six fluid pair s with R22 as the refrigerant and different absorbents: DMA; DMF; DMET EG; DMETrEG; DMEDEG; and NMP are considered, Variations in COP, circul ation ratio, percent mass of generated vapour utilised for transfer-ta nk operation, and minimum generator temperature are compared over a wi de range of operating conditions. In general, R22-DMA, R22-DMF, and R2 2-DMETrEG are preferable for a transfer-tank operated VARS. At high ge nerator temperatures or low condenser temperatures, R22-DMA gives the best overall performance. When the temperatures of the evaporator, abs orber, and condenser are high, one may prefer R22-DMF as the working f luid.