Ke. Yeager et al., MODELING OF EMERGENCY DIESEL GENERATORS IN AN 800-MEGAWATT NUCLEAR-POWER-PLANT, IEEE transactions on energy conversion, 8(3), 1993, pp. 433-441
Computer models have been developed of emergency diesel generators and
their associated emergency core cooling system induction motors durin
g sequencing and results compared with field tests. Models required to
perform studies of emergency diesel generators in a nuclear plant are
presented. Field measurements indicating different response of two se
emingly identical generator excitation systems are discussed. Results
of 480 volt ac contactor dropout testing are provided for determining
voltage limits in the 480 volt system during motor starting transients
.