NATURAL-CONVECTION BETWEEN A VERTICAL CYLINDER AND A SURROUNDING ARRAY

Citation
Dm. Mceligot et al., NATURAL-CONVECTION BETWEEN A VERTICAL CYLINDER AND A SURROUNDING ARRAY, Nuclear Engineering and Design, 146(1-3), 1994, pp. 267-276
Citations number
23
Categorie Soggetti
Nuclear Sciences & Tecnology
ISSN journal
00295493
Volume
146
Issue
1-3
Year of publication
1994
Pages
267 - 276
Database
ISI
SICI code
0029-5493(1994)146:1-3<267:NBAVCA>2.0.ZU;2-M
Abstract
The generic situation considered is natural convection between a singl e heated, vertical cylinder and a surrounding array of cooler vertical cylinders in a triangular pattern. The ratio of the test section temp erature to the cooling tube temperature was varied up to 2.6 by adjust ing the electrical power. The Rayleigh number, based on test section d iameter and air properties evaluated at cooling tube temperature, rang ed from 2.9 X 10(4) to 4.6 X 10(5). Results indicate that the convecti ve heat transfer data could be approximated as Nu(D)(T(ts)/T(ct))0.14 = 0.156 Ra(D)1/3 in the apparent turbulent region for Ra(L) > 1.2 X 10 (11).