Jy. San et Gd. Jiang, MODELING AND TESTING OF A SILICA-GEL PACKED-BED SYSTEM, International journal of heat and mass transfer, 37(8), 1994, pp. 1173-1179
A two-column packed-bed desiccant dehumidification system is tested an
d analytically modeled. The results are consistent. The desiccant is a
spherical silica gel particle with an average diameter of 5 mm. The l
ength of the columns are individually 9, 15 and 24 cm. Three regenerat
ion temperatures are used, namely, 65, 75 and 85-degrees-C. An optimum
operating time period is obtained. The heat and mass transfer is anal
yzed by using a solid-side resistance method with consideration of a f
luid friction effect. The magnitude of the fluid friction effect is go
verned by the Reynolds number and a nondimensional length factor. For
a long column or a high inlet air velocity the fluid friction effect b
ecomes significant.