A. Pongratz et al., IMPACT OF MATERIAL OF WATER-SUPPLY SYSTEM S ON PREVALENCE OF LEGIONELLA SP IN AN HOSPITAL, Zentralblatt fur Hygiene und Umweltmedizin, 195(5-6), 1994, pp. 483-488
In this paper the prevalence of Legionella in water samples from cold
and warm water supply systems made of copper, iron and polyethylene wa
s determined. Water supplied by copper pipes revealed to be nearly fre
e of Legionella (only 2% of probes positive), but water from iron (90%
) or polyethylene pipes (65% probes positive) proved to be heavily con
taminated. The 82 isolates were identified as Legionella pneumophila,
one from serogroup 1, the others from serogroup 4.