1ST LAW THERMODYNAMIC EVALUATION AND SIMULATION OF AMMONIA-WATER ABSORPTION HEAT-PUMP SYSTEMS

Citation
Sn. Mumah et al., 1ST LAW THERMODYNAMIC EVALUATION AND SIMULATION OF AMMONIA-WATER ABSORPTION HEAT-PUMP SYSTEMS, Energy conversion and management, 35(8), 1994, pp. 737-750
Citations number
NO
Categorie Soggetti
Energy & Fuels",Mechanics,"Physics, Nuclear",Thermodynamics
ISSN journal
01968904
Volume
35
Issue
8
Year of publication
1994
Pages
737 - 750
Database
ISI
SICI code
0196-8904(1994)35:8<737:1LTEAS>2.0.ZU;2-8
Abstract
A thermodynamic analysis and evaluation of three types of ammonia-wate r heat pump systems have been carried out. The types are: conventional , experimental and reversed. Performance plots are presented for the c onventional and reversed systems, while relevant comparisons have been made between the same. The plots are quite handy for computer aided d esign and operation of such systems. Results from the evaluation of th e experimental system indicate areas of inefficiency which are a resul t of the system's hardware. The theoretical simulation of the reversed system indicates that the feasible range of operation of this system is very limited because of the low condenser temperature and, thus, lo w heat sink temperature it requires to operate effectively. Similar pr ocedures can be extended to related systems.