To replace an aging multiplexed observation system of about 1500 analo
g signals originating in 5 machines of the CERN PS Complex a VXI syste
m consisting of various oscilloscope and multiplexer modules housed in
local crates has been developed. The crates are linked together via a
n Ethernet cable and run under the VxWorks operating system. An on-lin
e Oracle database allows for reference signals and observation setting
s to be saved and restored. The signals are displayed within one hundr
ed milliseconds after their capture on virtual oscilloscopes on DEC wo
rkstations; these oscilloscopes include all the usual features plus th
e specific controls related to the CERN context. Two systems accessing
about a hundred signals, were delivered in March 1993 as a part of th
e PS-SL controls rejuvenation project. This paper will describe the ha
rdware and software structure, the current and expected performances a
s well as costs and forecasts.