The passages of vapor flow and the returning liquid flow, are perfectl
y partitioned in a separate thermosyphon. Therefore the flooding limit
can be eliminated, and practicability based on its construction is hi
ghly evaluated. In the present work, a container tube made of heat res
isting glass, in which an electric heater is inserted, is selected as
the heating section of the experimental equipment. Distilled water is
used as the working fluid. The influence of the heater type, the diame
ter of evaporating section and the liquid fill charge on the heat tran
sfer performance have been studied. The larger heat transfer coefficie
nt is achieved in the case of the U type heater, the larger tube diame
ter and the less liquid fill charge of the evaporating section. The us
eful correlation equations of the heat transfer coefficient in the eva
porator have been derived.